Skip to main content

Featured post

Surge Protector Installation Best Approach

Earthed and Unearthed System

Methods of Earthing
In theory, the main power network does not have to be earthed and sometimes arguments are put forward that an unearthed network may be more reliable. In some cases this can be true, but generally an unearthed networks can be unreliable due to influence of electrical or some other factors.
There are a number of ways in which an electrical power system can be operated –
- Unearthed or insulated system- High impedance earthed and- Low impedance earthed arrangement

Unearthed system/IT earthing system
In this kind of installation, there is no formal connection to earth because there may be some high impedance connections for instrumentation e.g coil of a measuring device.

Earthed vs Unearthed Electrical cable
In some generators and transformers, the star point is solidly grounded. This is called Earthed Electrical system.

In a three phase earthed system, phase to earth is 1.732(sqrt 3) is
solidly earthed system
higher than phase to phase voltage.

In unearthed system (with neutral not grounded) phase to ground voltage can be equal to phase to phase voltage. In such case, the insulation level of conductor to armor should be equal to insulation level of conductor to conductor.

 Unearthed System 
In bigger installation e.g. generators of bigger capacities like 500MVA fault level are very high and in case of an earth fault, heavy current flows into the fault and this lead to damage of the transformer or generator.
To reduce this fault current, star point of the system is connected through a resistance. If an earth fault occurs on one phase, the voltage of the fault with respect to earth appears across the resistance.
Therefore, the voltage of the other two healthy phases with respect to earth rises by 1.7 times. If the insulation of these phases is not designed for these increased voltages, they may develop earth fault.
Since the phases are not grounded in this kind of installation, there are chances of getting shock while operating the system. Hence the insulation level for cable for unearthed system has to be more than insulation level for earthed system.
Also, an unearthed system is not suitable for smaller generators and transformers especially for houses.
Unearthed system


For instance
Imagine an earthed star connected system. Imagine a TV is connected to phase L1. Image a short circuit occurs on Phase L2. The equipment on the two good phases is good, because the star point has been connected to earth.If the star point was not earthed, the other two phases will raise their voltage by an additional root 3 (1.732), so the connected TV will sizzle and eventually burnt into flames.

The greatest difference arises in the voltage grade (Uo/U), which is:
Earthed System
Unearthed System
1.9/3.3kV, 3.3/6.6kV, 6.35/11kV, 12.7/22kV and 19/33kV
3.3/3.3kV and 11/11kV

In an exception to the above, the cables of 6.35/11kV for an earthed system can also be used in the place of 6.6/6.6 kV for an unearthed system. This is because each core of the cable has the insulation level to withstand 6.6kV due to which between core to core insulation level will be 6.6kV+6.6kV = 11kV.
 Earthed System 
An earthed system is the one in which the star point of a generator or transformer is solidly connected to the mother earth.
In three phases earthed system, phase to earth voltage is root 3 (1.732) times less than phase to phase voltage. Therefore voltage stress on cable to armor is 1.732 times less than voltage s tress between conductors to conductor.
 Differences 
- Cabling
So, 11kV earthed cable can be used in place of 6.6kV unearthed system since the cable manufacturing process is the same. The size of the cable will depend on the current rating and voltage level. So,
Voltage grade (Uo/U) where Uo is phase to earth voltage and U is phase to phase voltage
Earthed system has an insulation grade of kV/1.75x kV
For earthed system (Uo/U): 1.9/3.3 kV, 3.8/6.6 kV, 6.35/11 kV, 12.7/22 kV and 19/33 kV
Unearthed system has insulation grade kV/kV
3 phase 3 wires system generally comes with unearthed grade cable and 3 phase 4 wire systems can be used as earthed grade cables.

- Preferable for MV Transmission

For MV transmission, earthed cable will be more economical, but unearthed cable offers more insulation. This is because, if an earth fault occurs in the underground system, the voltage between the healthy phases and the ground will be equal to phase to phase voltage - 11kV or 6.6kV and higher insulation level is required. The voltage of the healthy phases rises by nearly 1.7 times resulting in an earth fault since the insulation of these phases is not designed for increases voltage. It is advisable to opt for an unearthed cable so that the core insulation has enough strength.

- Insulation Level
Unearthed cable requires more insulation strength than earthed cable. If a fault occurs in the phase to ground voltage is √3 time the normal phase to ground voltage. So, if an earthed rated cable is used in an unearthed system, it may result in an insulation puncture. Hence, it is essential to use unearthed rated cable in such situations, especially in the case of 6.6kV systems where resistance type earthing is used.

Comments